Section 10-2.07 / Warehousing for eco-friendly parts

Storing eco-friendly vehicle parts

In this chapter

In this chapter

Page 202 Original PDF

INSTALLATION EQUIPMENTSTANDARD OF ECO-FRIENDLY PARTS WAREHOUSE

    1. Eco-friendly Parts Warehouse Standard As there are no establishment of domestic and overseas EV battery related storage laws (as of August 2021), referred to similar standards and recommendations from the fire department. MOBIS established its own standards. Administrative rules or recommendations from firefighting authorities/insurance companies stated in the above related laws Consulting results from HQ relevant departments (electrification BU and Safety Dept.) On-site inspections (e.g. Eco-friendly warehouses, packaging companies, etc.)
Type List
Warehouse Conditions Mandatory Temperature below 35℃ ( EV battery) Temperature between 0℃ ~ 35℃ (Fuel cell) Installation of thermo-hygrometers
Safety Facilities, Equipment Mandatory Fire blanket and fire extinguisher Fire-fighting facility(fire detector, sprinkler, tacks) Smoke-ventilation facility for worker
Recommend Cooling facility(ex. Ceiling fan)
Storage Location Mandatory If stored in a separate area of the warehouse, mark the area and separate it 3 m from the rest
Recommend EV Batteries: Defined as Dangerous Goods (in some countries) - Store in EV-dedicated warehouse or at segregated storage area near by exit - Comply with “Separated area” regulations if authorities have rules ※ Fuel cell : not classified as “dangerous goods”
Storage Rules Floor Mandatory Stacking level : 4 or less (if necessary, temporarily 6 floors, If overloading is continued more than 6 months, make an alternative plan
Recommend layout : Place below 4 rows Calculation for required area (4 levels) standard: Parts size (WXD) x 0.62 Multi-row: Parts size (WXD) x 0.5
Rack Recommend Load spec: 1.2ton per cell / Stack 1 level in a cell
Page 203 Original PDF
  • ① Warehouse Facility

Name Picture
Establishment/rental of an EV-parts Dedicated warehouse HQ’s EV-parts dedicated WH
Operation in existing warehouse Example
  • ② Equipment

Name

Thermo-hygrometers Fire blanket Fire extinguisher (A-C) Fire detector
Exhaust fan Ceiling fan water tank
Page 204 Original PDF
    1. Warehouse Facility The following equipment specifications refer to provisions by the fire departments and insurer of various countries. In case of rental/setting up new warehouse, please comply with the recommended specifications and check the following standards.

Type Item Usage Checklist Photo
Mandatory (Installation) Fire-fighting facility (Fire detector + Sprinkler) Automatically spray water on fire M) Install fire detectors in warehouse Installing sprinklers apart from 2-3m between them ※ Install sprinklers in case of self-construction
Recommend (Specification)
Mandatory (Installation Smoking- ventilation facility (Exhaust fan, Ventilation duct) Exhaust smoke inside the warehouse in case of fire M) Install exhaust fan and ventilation duct
Recommend (Specification)
Recommend Cooling facility (circulating fan, cooling duct, air-conditioner) Manipulate temperature R) Use of air conditioners in hot and humid countries R) Install when the annual highest temperature is more that the current temperature standard (35℃)
Page 205 Original PDF
    1. Storage Facility The following specifications is recommendation and can be modified among your own warehouse environment. But please check the fire authorities rule before installation of Rack facilities.

Type Spec Usage Checklist
Recommend The rack specification - It is a “recommended” and can be changed depending on the case. - However, It is “necessary” to observe the loadable weight per cell : 1.2ton Reference) Load/Tie Beam Spec. Beam Type Pcs/cell Remarks Load Beam W : more than 2ea (Front Beam) 100m Tie Beam 3ea - Install the rack after checking law, regulations : whether sprinklers is mandatory, etc. - Install the rack after checking the floor loading capacity Stack one part per cell
Beam Type Pcs/cell Remarks
Load Beam (Front Beam) 2ea W : more than 100m
Tie Beam 3ea
Page 206 Original PDF
    1. Safety Equipment The below equipment are “Mandatory” But the specifications for each equipment are "recommended” specifications, and laws and regulations of each country take precedence (refer to the fire fighting laws of each country for the spacing of fire extinguishers, etc.)

Type Item Usage Checklist Photo
Mandatory Thermo- hygrometers Temperature and humidity measurement M) Locate near the EV-parts storage area R) Measure both the top and bottom of the rack (If necessary, locate it in several places)
Mandatory Fire extinguisher (A-C) Initial firefighting in warehouse Required to have all A-C-class specifications or integrated fire extinguishers 2 fire extinguisher specifications (2 each per spec.) per equipped location (see the photo on the right) Gaps of equipment (domestic standard, selected from the following conditions) - Place per 20m walking distance (2 types, 4ea) - Place per 200m2area (2 types 4ea) Recommended the total weight of the fire extinguisher is 7 kg or less to respond to fire timely ※ Based on NFSC, NFPA
Mandatory Fire blanket Initial fire, external isolation, complete combustion M) Prepare at least 2 types of blanket Use Blanket that is wide enough to cover the product ① 3m × 2m : It is essential to be equipped in logistics equipment, is placed in all equipment, and 1ea is placed near the storage area and the entrance door, respectively ② 5m × 5m : For complete fire extinguishing (using yards), equipped with 1ea each near the storage area and the entrance door - Fiberglass : minimum thickness of 800 g/m2 (jet flame protection) ※ Usage : refer to Fire Evacuation procedures ※ Quantity : the number of EV-Parts logistic equipment +1
Page 207 Original PDF
    1. Personal Protective Equipment For Fire Fighting The equipment is “required” to be equipped with all logistics equipment operated at all times (“Recommendation” to work with safety protective equipment and insulating materials if necessary) Equipment specifications must be equipped with additional equipment that meets both the “recommended” specifications and essential specifications in accordance with laws and regulations of each country.

Item Usage Contents Photo
Fire fighting helmet Hair protection To prevent battery impact, fall, or injury in case of electric shock when responding to fire Use of products certified UL 2
Protective clothing Physical protection A fire-fighting special fireproof suit which is usually yellow (different from regular fireproof suit) In the case of a battery fire, toxic substances that can penetrate the skin occur (HF), so skin protection with fireproof clothing is essential Use of products certified UL 2
Air respirator Respiratory protection Respiratory protection from toxic gases generated in the event of a fire. It consists of a high-pressure air container, a face body, a supply valve, an exhaust valve, a pressure reducing valve, a back burner, a pressure gauge, an alarm device, and an air supply hose. When wearing a face body, preventing the inflow of fire and protecting the face. Use of products certified UL 2
Heat-dissipating gloves Hand protection Protection of workers' hands and wrists from high heat and harmful substances in response to fire Recommended to use as thick as possible Use of products certified UL 2
Fire safety shoes To prevent electric shock Protection of the operator's foot, foot, and ankle area in response to a fire Reduction of the risk of electric shock that may occur when responding to a battery fire by using an aqueous fire extinguishing method Use of products certified UL 2
Page 208 Original PDF
    1. Logistics Equipment All Specifications are recommended. It is possible to use branches’ own logistic equipment But It is necessary to use that can safely handle the weight of the part and fork extensions are not recommended because of thickness.

Type Item Checklist Remark
Recommend (Partially) Fork-Lift Place of use: in/outbound area, Floor Equipment Specifications - Power type (loadable weight) : Electric (2.5t), Diesel (3.5t) - Fork : 1) Length : more than 1800mm 2) width : less than 130mm 3) thickness : less than 90mm (Based on the thickest part of the fork) The fork must be long and wide enough to withstand the weight of item. The forklift fork extensions are not recommended because of thickness. The thickness must be thin thinner the fork tube(100mm).
Recommend (Partially) Reach Truck Place of use: Floor/Shelf rack area Equipment Specifications - Power type (loadable weight) : Electric (1.8t, 2.0t, 2.5t) - Fork : 1) Length : more than 1800mm 2) width : less than 130mm 3) thickness : less than 90mm (Based on the thickest part of the fork)
Recommend (Partially) VNA(3 WAY)
Page 209 Original PDF

Type Back camera Safety light Headlights Rear light Backward alarm Warning light Speed limit
Forklift (Sitting type) ● ● ● ● ● ● ●
Forklift (Sitting type) - ● ● ● ● ● ●
Forklift (Sitting type) - ● ● ● ● ● ●

Back detector · Safety light · Safety device (speed)

Detection/alarm at close distance Visualize “caution” by recognizing Complies with the speed of

to prevent collisions between · the location of logistics equipment operation of equipment in the logistics equipment and workers · to nearby workers · workplace

Person recognition camera (AI) · Installation of safety lights at the · Installation of a speed limiter

    1. Possible to check the back · front and rear : A light of 2,000 · (recommended)
    1. Watch out for the driver of the lux or higher, a lamp LED type, · 1) Indoor work logistics display and sound alarm when etc. · equipment : 8km.

For indoor work logistics equipment

the rear camera recognizes a · 2) Outdoor work logistics person · (excluding outdoor use) · equipment : 10km (8km for

both indoor and outdoor use,

※ Recognition of installation of · ※ The color of safety lighting can · reinforced) equivalent or higher performance · be changed by workplace in safety devices suitable for the · consideration of the color of the※ As a recommended installation purpose · floor of the site. · device, non-installation and

※ Recognition of installation of · operation workplaces continue to equivalent or higher performance · comply with the relevant worker’s safety devices suitable for the · driving speed regulations / purpose (e.g., rear → line light · strengthen safety marker installation and operation)

Page 210 Original PDF

ECO-FRIENDLY PARTS HANDLING

    1. Fire Related Laws There is no firefighting law related to EV battery : Refer to standards for similar items (dangerous goods) and overseas firefighting regulations, etc.

South Korea : Refer to the Research Report on Fire Safety Measures for Energy Storage Systems

  • Place all classes of extinguishers (A: ordinary combustible materials, B: flammable liquids, C: electrical equipment) International :
  • Should Comply with the standards for extinguishing electricity storage facilities and the management regulations of dangerous goods in the standard test (UL9540A) of safety test methods
  • Storage/response laws and recommendations from fire authorities related to dangerous goods in each country should be prioritized
    1. MOBIS Standard Create a Fire Emergency Procedures(Action plan) Share fire extinguishers and fire extinguishing equipment standards Make a separated space (water tank, yard) for fire response (At least one option must be secured) Option1) Water Tank : The headquarters produces and distributes standard specifications (’22) Option2) Yard : A flat space of 10m X 10m or more must be secured in the warehouse site, and floors must be marked, and emergency response areas must be marked in the relevant area
Page 211 Original PDF
    1. Fire Fighting Process W/ Water Tank

Text from figure
  • ① Recognize the fire Alert building occupants a fire Press the emergency bell to spread it to the entire area

※ Report the fire to authority

Text from figure
  • ② Take safety gears Who are in charge of fire-fighting wear personal protective equipment

Text from figure
  • ③ Initial fire-fighting First-aid fire extinguishing ASAP (Act in groups of two)

Text from figure
  • ④ Delay the flame Cover the item with fire blanket In case of thermal runaway, cover it with blanket after fire extinguishing.

Text from figure
  • ⑤ Move the part to tank Move to the water tank.

Text from figure
  • ⑥ Battery completely discharged Put the item in the tank and wait the battery completely discharged

※ The salt-water temperature rises to 90℃ ※ 12hr. or longer confirmation required

※ In order to comply with the fire evacuation procedures, it is necessary to prepare a water tank ※ Please refer to the page “Safety/Emergency Response Precautions “, create Emergency Task Force and rehearse all procedures

Page 212 Original PDF

W/O Water Tank

Text from figure
  • ① Recognize the fire Alert building occupants a fire Press the emergency bell to spread it to the entire area

※ Report the fire to authority

Text from figure
  • ② Take safety gears Who are in charge of fire-fighting wear personal protective equipment

Text from figure
  • ③ Initial fire-fighting First-aid fire extinguishing ASAP (Act in groups of two)

Text from figure
  • ④ Delay the flame Cover the item with fire blanket In case of thermal runaway, cover it with blanket after fire extinguishing.

Text from figure
  • ⑤ Move the fire extinguish zone Move to the fire extinguish zone

※ Pre-designation of quarantine area is a must

Text from figure
  • ⑥ Battery completely discharged When accessible, cover the part with fire blanket and wait for combustion

※ Before preparing the water tank, make a fire extinguish zone and move damaged part to the zone(yard) ※ Stand by until natural discharge and combustion completely.

Source note: The equipment named in this sentence conflicts with step 6 on the same printed page. Confirm the wording with MOBIS before using this step.

※ By configuring an emergency response task force (see details), prior understanding of the above process and simulation training are essential

Page 213 Original PDF
    1. Fire Prevention Inspection Checklist Check your own fire authorities’ checklist, first-All the lists must be checked periodically (e.g. monthly)
Contents Checklist Adequate Inadequate Remarks
Warehouse Check Is the EV-battery & Fuel Cells are stored separately in the isolated place? Are ventilation, fire-fighting facilities operating normally? Are fire blankets and fire extinguishers located at the place as good condition? Are there any traces of leaks or a risk of fire? Are there any combustibles around the storage area?
Stocks Check Do periodic inventory checks and is there any damaged parts? Are there any over-loaded parts? Are there any EV-batteries mixed with general parts? Are there any EV-batteries stacked different size parts?
Firefighting Facilities Are the fire extinguisher pressure gauges in the normal range? Is there any external damage of fire extinguisher(handle/ safety pin)? Are the indoor fire hydrant cabinet, hoses, valves in good condition? Is there no burden in front of the fire hydrant? Is the automatic re-demagnetizer number/transmitter on? Is there any damage to the exterior of the sprinkler head? Are the Emergency(Escape) Lighting always on? Are the fire doors always closed? Are there any obstacles in the evacuation stair/way?
Page 214 Original PDF
    1. Safety/Emergency Response Precautions It is essential to establish an evacuation plan for each base (including the location, route, and evacuation guidelines for evacuation facilities) and conduct education and training once a quarter of implementation.

Safety Precautions

  • ① Cautions for safety
  • Certificate logistic equipment worker and periodically educate safety provisions of OSHA
  • Prepare and check the location of personal safety equipment
  • Prepare the fire-fighting facilities and equipment
  • Periodically educate and rehearse fire evacuation procedures regularly, Create Emergency Task Force
  • ② A Fire Emergency Procedures(Action plan) -details are in the procedure page
  • In case of damage of parts due to collision accidents (exposure to electrolyte, damage to separator, etc.), put fire blankets on the item and remove it to the prepared area(water tank, yard)
  • Periodically check and update authorities’ laws and regulations

Emergency Task Force

Group Roles & Responsibilities #of members Name
Alertness Announce “Fire” in a loud voice Press the emergency alarm and notify everyone in the warehouse Report the fire to authority 2
Evacuation Execute the existing evacuation procedures Operate the emergency contact network and confirm the number of people Make sure everyone has evacuated 4
Fire- extinguishing Wear personal Protective Equipment (PPE) Use fire extinguisher on a fire and throw a fire blanket on the part If accessible, move the part with a forklift to yard or water tan 2
Completion Wear personal Protective Equipment (PPE) Stand by at the fire extinguish zone/water tank If accessible, cover a fire blanket on the fire Wait in the safe area until the fire station arrives 2
Page 215 Original PDF
    1. Floor Storage

Details Examples
Stacking Stacking level : 4 or less (if necessary, temporarily 6 floors, If overloading is continued more than 6 months, make an alternative plan Calculation for required area (4 levels) ① Standard: Parts size (W × D × 0.62) ② Multi-row: Parts size (W × D × 0.5) Stack only with same part packed with same package material Load by aligning the slot of pallets Correct Wrong
Stack up by changing directions Weight biased risk due to battery shape Stack up boxes with weight balance (Change the direction of the boxes stacking up) ※ It is weight biased toward the side with the HEAVY label attached HEAVY HEAVY HEAVY HEAVY HEAVY HEAVY HEAVY Weight biased Example of stacking
Page 216 Original PDF
    1. Forklift Handling

Details Examples
Stacking The center of gravity is shifted to one side because of the weight biased shape Handling with multi level of parts might be caused the danger of weight bias H E A V Y
Handle the forklift by pushing the fork all the way to the innermost part of the pallet. Especially, when forking in the longitudinal direction, the heavy side should come toward the machine Y V A E H
Page 217 Original PDF
    1. Load in the Vehicle

Details Examples
Do not stack different kinds of parts when shipping or waiting shipment. Especially, the small/heavy parts might cause weight concentration on the upper side of the box Recommendation of fixing and separation to prevent movement of parts within the vehicle
For small cargo truck(w/o cover) Fix the parts well and use the waterproof cover. (even if it doesn't rain) Correct Wrong
Page 218 Original PDF

WAREHOUSE ENVIRONMENT CHECKLIST

    1. Eco-Friendly parts warehouse environment checklist
Contents M/R Checklist Check Remarks
Insurance M Insurance for EV-parts Be different according to insurers
Warehouse Conditions Security R CCTV & Smoke control system
Temp. M Temperature below 35℃ in warehouse ※ For fuel-cells : 0℃ ~35℃
Ventilation R Installation of ceiling (or inside building) exhaust system Check the proper exhaust capacity
Fire-fighting M Mark firefighting facilities and organize surroundings
M Management of fire extinguishers (Placement, Operation check)
R Checking coverage of fire hose (If necessary, connect 2 or more)
R Installation of sprinklers
Safety management Equipment M Safety gears, fire blankets
Emergency Process M Creating/training/implementation of Fire evacuation procedures
M Creating/training/implementation of working process
Facilities M Periodical inspection of electrical facilities and cleaning up the surroundings
M Management of inflammable substances in designated areas
Operation management In / out-bound M Truck / forklift safety management (planning / training / implementation)
M Forklift driver qualification management and regular training
M Installation of forklift safety devices (rear camera, safety lighting, etc.)
M Handling just with a piece
M Stacking level in transportation: 4 or less (inland delivery)
Storage M Compliance with storage standards (loading less than 4levels, etc.) For storing on floor
M FIFO management